Introduction
Hello, and thank you for joining today’s white paper webinar. My name is Matthew Kahane. I am a software engineer here at PMI, and today we’ll be covering our white paper on voltage, current, and resistance, and what a power quality monitor actually measures. It’s the first paper in our series of PQ fundamentals, and everything else in the series builds on it.
Here’s why it matters. Every number your monitor shows you comes from just two measures. If you know what those two are and how the monitor gets them, you can trust your data. You can catch a bad hookup before it costs you a week of record.
A Power Quality Monitor Only Measures Voltage and Current
I’ll start with something that sounds a little backwards. A power quality monitor doesn’t actually measure power quality. It only measures voltage and current. That’s it. Thousands of times per second. Everything else it shows you is math on those two.
Take a look at this picture right here. This is a Bolt installed into a panel. Looks like there’s a lot going on, but really there’s only two kinds of wires here. These ones right here are hooked up directly, and these are the voltage leads. And then these orange loops up here are the current sensors, also known as the flex CTs.
Now, here’s the interesting part. Those two kinds of wires work in completely different ways. The voltage leads touch the circuit, and the current CTs specifically don’t. That’s on purpose. By the end of the day, you’ll know why, and you’ll know why it matters every time you hook up one of these.
What Voltage Actually Is
Voltage is the difference between two points. Technically, it’s the difference in energy per unit charge between those two points, and it’s measured in volts. The word to hang on to is difference. Voltage always has two ends.
Here’s an example. Say I tell you a balloon is ten feet high. You probably pictured it ten feet off the ground, but I never said off the ground. It could be ten feet above a building. Ten feet high doesn’t mean anything until you know above what. Voltage works the same way. It’s a hundred and twenty volts. Okay, between what?
You probably hear people say this line is a hundred and twenty volts all the time, and usually they mean a hundred and twenty volts between that line and ground. That’s the same thing we did with the balloon. You just assumed the ground. And because everybody assumes it, people use potential and voltage pretty much interchangeably.
When you’re actually taking a measurement, you can’t assume anything. Every voltage reading is point A to point B, phase to phase, or phase to neutral. Look at the voltmeter here. Two leads, one on each side of the resistor.
So this is the first practical rule for today. You can’t measure voltage from one connection point. One voltage lead by itself measures nothing. It needs something to compare it against. That’s why our monitor has a neutral lead, and that’s why it matters where you land it.
What Current Actually Is
If voltage is a difference, then current is a flow. Current is the charge moving through a wire. It’s measured in amps. It’s how much charge goes past a point every second.
Now, here’s the part that trips a lot of people up. In a simple loop like this, the current is the same everywhere. Before the bulb, after the bulb, and back at the source, half an amp, half an amp, half an amp. The bulb doesn’t use up current. The same current comes out the other side.
So if the bulb isn’t using up current, what is it using? Something has to get used to make the light and the heat, and that something is energy. The charges carry energy as they move. When they go through the bulb, they give up some of it as light and heat, then they keep going around the loop. Same flow, less energy.
And that ties right back to voltage. Voltage is the difference in the energy per charge, remember? So if the charge loses energy going through the bulb, there’s a voltage across the bulb. That’s exactly what the voltmeter in figure two is reading. So current is a flow. Voltage is the energy the charges give up along the way. Two different things, and the monitor has to measure both.
Resistance and Ohm’s Law
So what decides how much current flows? Resistance. Resistance is how hard it is for charge to get through something. It’s measured in ohms. Everything has some sort of resistance, even a good copper wire. A resistor is just something that has a lot of it.
When you push charges through a resistor, it loses energy as heat, and in a light bulb, as light as well. So that glow you see is exactly what the resistance is doing.
Here’s the relationship. The source sets the voltage, the component sets the resistance, and the current is whatever falls out. That’s Ohm’s law. V equals I times R.
Let’s try it. Say we’ve got a light bulb with two hundred and forty ohms of resistance on a hundred and twenty volt circuit. Current is voltage over resistance, a hundred and twenty divided by two hundred and forty, half an amp. Now, multiply voltage by current, and you get power. That’s energy per second in watts. A hundred and twenty volts times half an amp is sixty watts. So that’s a regular sixty-watt bulb. One example, and every other number on the slide falls out.
Now look at what power is, voltage times current. That’s the two things the monitor measures. The monitor never measures power directly. It calculates it, sample by sample, from voltage and current. So if either of those are off, your power is off too. Hang on to that. It’s going to come back in a few minutes.
DC, AC, Impedance, and Loads
We’ve got a couple more terms, and then we’ll look at the monitor. First is DC, also direct current. Flows one way all the time. AC, alternating current, keeps reversing. On a sixty hertz system, it flips directions a hundred and twenty times a second. Most power systems in the world run on AC. Why is a story for a future paper.
Since AC keeps changing, resistance isn’t the whole picture. AC circuits have something called impedance. That’s the resistance plus a few effects that depend on frequency. We’ll get to those later in this series as well.
A load is anything on the circuit that draws current. A light bulb, a motor, a computer, a whole building. These are all considered loads. And there are two kinds of loads. There’s a linear load where you double the voltage and you double the current. The ratio stays the same no matter what. There’s also nonlinear loads where it doesn’t, and nonlinear loads are behind a lot of power quality problems, so we’ll definitely be coming back to them. For today though, just remember that loads draw current and the monitor has to measure that current.
How the Monitor Measures Voltage and Current
This is where it all comes together. A PQ monitor has two sets of connections that line up exactly with what we just covered. Voltage is a difference between two points, so the voltage leads connect right to the circuit, one on each side. The monitor sits in parallel with the load, just like that voltmeter in figure two. Inside, a resistive divider scales the voltage down to something the electronics can handle.
Now current is different. Current is a flow. To measure it the old-fashioned way, the current has to flow through your meter. That’s an ammeter in series. To put an ammeter in series, you’d have to cut the wire and hook the meter up to both sides. Now picture doing that on a live four hundred amp feeder. You have to break the circuit, which shuts down whatever you’re feeding, and be working on an energized conductor to do it. That’s not happening, so we need another way.
Here’s the trick. When current flows through a wire, it makes a magnetic field around that wire. So we don’t measure the current directly, we measure the magnetic field that it generates. No cutting, no contact. That’s what clamp-on current sensors do. That’s why your current leads go around the wire instead of touching it.
Iron Core Clamp CTs vs. Rogowski Coils
There are two main kinds. On the left is an iron core clamp CT. It’s a coil of wire wrapped around an iron ring, and the ring goes around the conductor. That makes them sensitive and accurate. The catch is that the iron can only handle so much. Push enough current through it and it saturates. The output stops keeping up, and your readings stop being accurate.
On the right side is a Rogowski coil. That’s what we call a flex CT. It’s a coil wound on a flexible form with no iron in it, and no iron means no saturation. There’s a trade-off, though. A Rogowski coil responds to how fast the current is changing, not the current itself. So the monitor runs that signal through an integrator to turn it back into a current reading. If you want the details, you can check out our flex CT overview paper, also available.
So why does the Bolt ship with flex CTs? It’s not about avoiding cutting the wire. Both kinds clamp on. It comes down to two things. First, they don’t saturate, so they handle huge ranges of current. And second, they’re flexible. They’ll wrap around awkward bus bars and fit into tight spots where a rigid clamp just won’t go. If you want to compare, we’ve got a paper on our TLAR and TLAR-S clamp style CTs as well.
Voltage leads that touch. Current sensors are leads that don’t. Two kinds of wire, two different ideas.
Four Practical Field Tips
Knowing how these sensors work tells you four things you’ll run into in the field.
- CT ratios. Sometimes you can’t get your sensor around the main conductor. Maybe it’s out of reach, maybe there’s no room. So you clamp around the output of a CT that’s already in the panel. Say it’s two thousand to five. When two thousand amps flow through the main conductor, the CT puts out five amps. Your monitor has no idea. All it sees is five amps. So you have to tell it the ratio, either on the device or in the recording afterwards. And if you get it wrong, every current reading is off by that same factor, and so is every power reading, because power is voltage times current. Here’s the sneaky part. Your voltage looks totally fine. Nothing jumps out at you. The data looks reasonable, but it’s all wrong. One quick note, PMI monitors recognize PMI’s own sensors automatically. So when you plug those in, you don’t need to set anything. It’s only when you’re reading through someone else’s CTs, like that panel CT, that the ratio is on you.
- Polarity. Current sensors care about direction. There’s an arrow on them, and it’s supposed to point towards the load. Put it on backwards, and the monitor thinks the current’s flowing the other way. And since power is voltage times current, your power comes out negative. It looks like the load is pushing energy back onto the grid. So if you ever see negative power on something that definitely isn’t generating, check which way your CTs are clamped on.
- What’s inside the clamp matters. A clamp reads whatever is inside it, added together. Clamp around a few parallel conductors, and you get their total. But clamp around the outgoing conductor and the return, and it reads zero. The current going out and the current coming back cancel each other out. And sometimes that’s exactly what you want, because if it doesn’t read zero, some current is going somewhere it shouldn’t, like leaking to ground. And that’s actually the same idea a GFCI outlet uses to decide when to trip. So that outlet in your bathroom is basically doing this measurement all day long.
- Safety: never open circuit an iron core CT. A traditional iron core CT makes a small current in its coil, and that current runs down the leads to the meter. Say you unplug those leads while the main conductor is still energized. That current has nowhere to go, but the magnetic field keeps pushing it anyway. The voltage across those open ends can climb to very lethal levels. So always short your two leads together before disconnecting them. Rogowski coils don’t have an iron core, so they don’t have this problem. And PMI sensors are built around it. There’s a resistor inside the housing, so the circuit’s never open, and both leads share one cable.
Wrap-Up
A power quality monitor only ever measures two things, voltage and current. Voltage is a difference, so the voltage leads touch two points. Current is a flow, so the current sensors read magnetic fields instead of cutting the wire. And everything else—power, RMS, harmonics, all of it—is math on those two things.
That’s why those four things matter. Wrong CT ratio, backwards arrow, the wrong wires in the clamp—any one of them throws off one of your two measurements, and then every number built on top of it is off as well.
Today, we treated voltage like a fixed number, a hundred and twenty volts, and that’s fine for DC. But the world runs on AC, where the voltage is swinging back and forth sixty times a second. So what does a hundred and twenty volts even mean? That’s the next paper in this series.
If you want to go deeper on current sensors in the meantime, you can check out our Measuring Current Best Practices paper. It picks right up where we’re leaving off here.
Thank you for attending today’s webinar. If you have any questions, you can reach us anytime by calling 800-296-4120 or emailing support@powermonitors.com. Thank you, and have a good afternoon.