Transcript
Introduction to the IEEE 519 Standard
Hello everyone, and welcome to today’s white paper webinar. The topic today is the IEEE 519 standard and how to generate these reports automatically from ProVision software.
Before we get into how to use the software, let’s talk just for a brief amount of time about the 519 standard itself and what it means and what type of measurements you need to generate this report. The 519 standard is the IEEE recommended practice for measuring limits for both voltage and current distortion. This was most recently updated in 2014 and includes a very rigorous definition of what needs to be measured, how long that measurement should last, and where that measurement should be taken.
Some important concepts for grading an IEEE 519 compliant report is to put the recorder in the proper location and also to compute a parameter known as the max demand load current.
Point of Common Coupling
The 519 standard is not really meant to be an equipment spec. It’s not a limit of harmonic distortion on a particular piece of equipment or at the substation. It’s intended to limit distortion at the point of common coupling, which is the closest point upstream that one customer could affect another customer. The intent of the 519 standard is to limit one customer’s ability to distort the voltage with their harmonic content in a way that would adversely affect another customer. So the measurements are really intended to be made at that point of common coupling.
Here’s the definition from the standard, but essentially what this is, is the closest point upstream where customers are connected together. This is usually the primary side of a transformer. For three-phase customers, if they’re on the same feeder, if you would add another customer to that circuit, you’d add a new transformer to them so that the closest point they’re electrically tied together is the primary side of the transformers.
This may not be the case in a residential situation. If, for example, you have a pad mount transformer that could feed multiple homes, if you would add another house to that secondary, then the secondary of the transformer is the point of common coupling. But in general, it’s the closest point upstream from that customer where another customer would be attached.
Measuring on the Transformer Secondary
So technically, the primary side is usually the point of common coupling, but that’s a very difficult place to make accurate harmonic measurements, and it also doesn’t allow you to isolate that customer’s current if you have a customer that either is causing harmonic distortion or complaining about harmonic distortion.
So most utilities, from a practical standpoint, measure on the transformer secondary, and that’s a conservative place to measure because harmonic distortion for voltage is generally worse on the secondary because you have the impedance of the transformer introducing another opportunity for a harmonic voltage drop. So if you’re meeting your voltage distortion limits on the secondary of the transformer, you’re almost certainly meeting them on the primary side also. That is a conservative place to measure.
Max Demand Load Current
The other important definition from the 519 standard is the max demand load current. This is denoted as IL in the standard. This is the official definition out of the standard, but what this is, is a representative maximum that the customer draws from that transformer.
The way to measure this is to each month determine the maximum thermal demand current of that customer, say a 15-minute average or a 5-minute average, not the peak one cycle current, but the maximum steady state current that customer draws each month, and then average all those 12 months together to give you an annual average.
That can be difficult to come up with. If you have 15-minute billing information for an entire year, you may be able to estimate this for the customer, but often you don’t. In most cases, utilities will do something like make a 30-day recording and find the maximum demand current in that one-month period, and then make any seasonal adjustments that they may know of or be aware of for the customer. Of course, if it’s a new customer that isn’t drawing current yet, or it’s a customer that is adding or expanding their footprint, then you don’t have that load to measure yet, so you certainly don’t have a year’s worth of data.
So that can be a little bit tricky to estimate, but it’s important to have a good handle on how you come up with this value because the customer current harmonics are scaled directly by this max demand current. So however you come up with it, you want to have a good rationale for how you did that, and it’s also useful to be able to change that value a little bit to see how sensitive the results are to small changes in that.
519 Standard Time Scales and Limits
The 519 standard has limits on two different time scales for harmonics. There’s a three-second time scale where harmonics are measured every three seconds, and then there is a 10-minute time scale. So the three-second value is the very short time harmonic measurement as denoted by the standard.
The terminology and notation in the standard is a little bit confusing, but the bottom line is every three seconds, the PQ recorder gives a new harmonic measurement, and that’s an aggregate of that three-second period. And then the 10-minute values are created from the three-second values, so there’s the short time harmonics. Since the 10-minute values can be computed completely from the three-second values, you don’t need to record both. The software can compute those 10-minute values for you, but you do need three-second values.
So to gather the data you need for a 519 analysis, record on a three-second interval, and then the software will compute these 10-minute values for you. There’s separate thresholds for three-second values and 10-minute values, so you need both to do a formal 519 analysis.
Voltage Distortion Limits
Here are the limits for voltage from the 519 standard. There are separate limits for different bus voltages at the point of common coupling. So keep in mind that even if you’re measuring on the transformer secondary, you would use the bus voltage for the true point of common coupling. So in a three-phase situation, the point of common coupling usually is the primary, so you’d be more often in this row, even if you’re making your measurement on the secondary. But if the PCC really is the transformer secondary, you’d use this under 1 kV row.
And if you’re up at transmission, remember too that this is not really meant to be applied at a transmission level unless that really is the point of common coupling. If you’re feeding substations or you’re feeding other utilities, that may be the point of common coupling. But generally, you wouldn’t be in this range unless that’s true.
There are limits for each individual harmonic in terms of a percent of fundamental, and then a limit on total harmonic distortion. These are meant to be measured as a Y, so you would need line and neutral measurements.
There are actually two different limits. You need a one-week recording, and in that one-week recording, the 10-minute values should be under the table limits 95% of the time. You would generally compute the 95th percentile in that recording and compare that directly to the table limits. There is a limit on individual or three-second values. So the 99th percentile every day is computed, and those values are compared to a value that’s 4.5 times the table limit.
So there’s actually two different thresholds. The 10-minute values, for example, use an 8% value, and the three-second values would use 1.5 times this or 12%. And this is done on a daily basis. So during that one-week period, you would have one comparison for the 10-minute values and a comparison every day for the three-second values.
Current Distortion Limits
The situation is more complex for current. Here is one of the current distortion limit charts from the 519 standard. For current, we have separate limits for different ranges of harmonics. So third through the 11th, 11th through 17th, all the way through the 50th. Those all have different ranges. And then we have a limit on total demand distortion, TDD, which is similar to THD for voltage, but this has the scaling of the harmonics to that max demand load current. In fact, all of these harmonics are all scaled towards that IL, that max demand load current. So any percent error in this estimate translates directly to an error in that current measurement.
Another complication is that the limits are different for different ratios of short circuit current to max demand load current. And that short circuit current measurement is made at the point of common coupling, and this ratio is a measure of how stiff the system is relative to that customer’s current draw.
The idea is that if it’s a really stiff system, if you’re in the hundreds or thousands, the customer will not have much ability to alter the voltage distortion or the current distortion. If it’s a really stiff system, they’re not going to be able to pull that voltage much. And so the limits are very high, 20% TDD, because it takes that much distortion to alter the voltage if the source impedance is that low compared to what the customer can draw.
On the other hand, if you’re at under 20, that’s a really weak system. It doesn’t take much current distortion to actually alter the voltage distortion. So the limits are very small, 5% TDD and very small limits for individual ranges of harmonics.
Keep in mind that even if you’re measuring at the transformer secondary, if you’re isolating that customer’s current, the short circuit current is the primary side short circuit current. These are also Y measurements, and here we have three different thresholds. The 10-minute values actually have two different thresholds now, the 1.5 times the table and then the regular table limits, and two different percentiles over that week. And then the three-second values have a 2x multiplier for the table limits. So there’s actually three different thresholds that are applied to different time scales.
Footnote C: Power Generation Equipment
There’s one more important note for the current limits, and that’s footnote C, which states that all power generation equipment is limited to this row. So if the customer has any sort of onsite generation, if they’ve got rooftop solar or wind turbines, they automatically use the most strict row here, regardless of the actual ratio of short circuit current to max demand load current. So keep that in mind if you have a customer that has their own onsite generation.
And then finally, there are separate tables for different bus voltages. This is the one you’d be most likely to use, 120 volts through 69 kV. But if you are above 69 kV, you would use either the next table up or transmission over 161 kV, this table.
Setting Up the Revolution for 519 Data Collection
Now that we have these thresholds in mind, we can see that it’s actually fairly complicated just to determine the thresholds you’re using. You need to know the short circuit current, the max demand current, find the ratio, find the right row, and the multipliers are different for different time scales.
So to gather this data, you typically use a Revolution and initialize it to record harmonic subgroups. I’m going to show in ProVision rather than in the white paper. For example, if we look at the settings for Revolution, if you go to Advanced, there is a button that you can click, the Daily button. This sets all the parameters you need for a 519 analysis. It sets the interval to three seconds. It turns on voltage and current harmonic magnitudes. It enables harmonic subgroups, which are technically the type of harmonic measurements required by the 519 standard, and it turns on all the harmonics.
It also turns on some other useful parameters such as THD for voltage and current, and also frequency and flicker. But the minimum is the harmonic magnitudes at three-second intervals, and you would want to record for at least one week to generate that weekly data.
Once this data is gathered, ProVision will then compute the 10-minute values from the three-second values. If you don’t record all harmonics, and if you take some of these off or use a different interval, or you’re not using harmonic subgroups, ProVision will still run the report for you. You don’t have to use the Revolution set up exactly this way to get useful information out of the 519 report. But it won’t technically be a full 519 compliant situation.
Running the 519 Report in ProVision
Once you have this data in hand, then you can run the 519 report. You can go to Report, 519 Compliance, and you can get a separate report for the daily three-second values, the weekly 99th percentile, and the weekly 95th percentiles, and then also a summary.
I’m going to start with the summary. The first thing ProVision will do is prompt you for the parameters it doesn’t know: the bus voltage, the max demand load current, and the short circuit current. And also the checkbox, does footnote C apply? Is there any power generation at this location? If it is, that automatically picks that strict row.
The bus voltage should be the voltage at the point of common coupling, and the voltage at the recorder doesn’t need to have the scale factors applied. This number is only used to pick which table and which row to use. So you don’t need to have a scale factor in ProVision to bring the nominal up to that voltage.
You do want to make sure that the max demand current and the short circuit current are both in the same per unit basis. So if you’re measuring on the secondary side, you can either put them both with the transformer secondary ratio or put them both on the primary side, but just make sure it’s apples and apples. Because the only way that this is used is to form the ratio, and then this max demand load current is used directly for that current harmonic data.
So if you are using primary side scaling, make sure that the scale factor is entered in ProVision so that it’s an apples comparison. The max demand load current is in the same per unit basis as the raw measurements themselves.
Summary Report Results
Once you enter these, click OK, and it will generate the summary report. When it does this, it will go through the entire data set, compute those 10-minute values, compute the thresholds, compute the percentiles, and then apply those thresholds. It gives you a summary for each type of limit. There’s the daily limits for those three-second values, and then there are the weekly limits for the 10-minute values. It gives you a pass/fail for each day and for each week by channel.
If you have a partial day or a partial week, it’ll tell you that. For example, typically you’ll have a partial day at the end of the recording, and it’ll tell you what fraction of that day exists. A pass or fail on a fractional day or a fractional week may not be necessary or may not be an issue because that’s not a fully 519 compliant recording session. But you want the full weeks and the full days to count.
Detailed Reports and Sensitivity Analysis
The summary doesn’t give you the details. It gives you an overall pass/fail. You can also run this report on any of the individual types. Look here at the 99th percentile for the weekly, and here we failed on both weeks. It’ll highlight the harmonics that have failed for voltage or for current, and also give you the limits.
In some cases, it’s not even easy to determine what limit to use, and so it’s helpful for the software to tell you which limit it’s picking. Here it’s 5% for voltage for THD, 12% for current THD, and that’s based on the ratio of short circuit current to max demand current, which here is 36. It shows you that ratio and shows you the three parameters that you entered.
This is an easy way to get pass/fail and to see which harmonics are over the limit. But it’s also useful to rerun this report a few times to determine how sensitive it is to changes. For example, you can rerun the report—it caches the values you’ve entered and saves that with the data file. So if you run it again, it’ll have those values pulled up for reference. But you can change these at any time.
If you aren’t that certain about the max demand load current or you want to determine how sensitive it is, for example, if 12 is a better estimate, you can put that in. It’s useful to rerun this a few times to see how the results change based on small changes in max demand current or short circuit current to see how sensitive it is, because it’s possible that you may be on the cusp of one of these rows.
For example, if you’re right on the edge between under 20 and 20 to 50, a small change in the short circuit current estimate or max demand load current could change the thresholds and turn a passing situation into failing or vice versa. But also just a small change in max demand load current directly affects the measurements for current because all current harmonics and TDD are directly scaled by that max demand load current. So it’s useful to know how sensitive the result is to those sort of changes.
Summary
Jumping back to the white paper, that summarizes the 519 report in ProVision. It’s a way to very quickly generate the analysis based on a one-week recording at three-second intervals with all harmonics enabled. That takes up a lot of data. That’s about a gigabyte of information on a disk because that’s a lot of harmonic recording.
But you don’t always have to do that. You can record fewer harmonics or a lower interval and still run the report. It will run the numbers as best it can and give you some useful information. It may not be a fully official 519 compliant report, but it’s useful to do that to get some sense of where you’re at.