• Skip to primary navigation
  • Skip to main content

PMI

  • Home
  • Products
  • Library
    • Videos
      • All
      • Bolt Quality Tests
      • Promotional Videos
      • Support Videos
      • Power Quality Decoded
    • White Papers
      • All
      • Artificial Intelligence
      • Case Studies
      • Communications
        • All Communications
        • Cellular Communications
        • General Communications
      • Distributed Generation
      • IEEE Standards
      • Power Quality
        • All Power Quality
        • Analyzing Waveforms
        • Flicker
        • PQ Data Analysis
        • PQ Theory
      • Products
        • All Products
        • Boomerang
        • Boomerang SCADA
        • Box Recorder
        • Canvass
        • Eagle
        • Flex CT
        • Guardian
        • Merlin™
        • Meter Sockets
        • PQ Canvass
        • ProVision
        • Revolution
        • TLAR
        • Using PMI Recorders
      • Voltage
        • All Voltage
        • CVR
        • Voltage Sag
        • Voltage Unbalance
      • Harmonics
  • Training
    • All
    • PDH Eligible Classes
    • On-Site Training
    • Webinars
  • Support
  • Our Company
    • About
    • Contact
    • Join Our Team!
    • Receive our Newsletter
    • PQ Resources
    • Power Quality Solutions
  • Account
  • Cart - 0 items

Seeker Modbus Map

← Back to Videos

Transcript

Introduction to the Seeker and Modbus

Hello, everyone, and welcome to today’s white paper webinar. Today we’re talking about the Seeker and Modbus. Here in this white paper, we talk about using Modbus with the Seeker. I’m going to also talk a little bit about some Seeker basics.

Seeker Basics

The Seeker is a PQ recorder and monitor. It really is three different products in one. In some ways it’s like a cloud-based Revolution. It’s a power quality monitor, but also it’s designed to be used in the cloud or with a network situation. Like the Revolution, it has four voltage inputs and uses our standard CT inputs for Flex CTs or iron core CTs. It’s powered by the voltage that it’s measuring, like the Revolution. It’s outdoor rated as NEMA 4X, so you can use it outdoors.

It has a lot of networking options, and that becomes important when we talk about Modbus or DNP3. You can use Wi-Fi, you can use LTE cell communications, you can use Ethernet, you can also use Bluetooth. It also has an option for GPS. You can have GPS time synchronized data. That allows you to correlate data with other devices or combine data with, say, a device at the substation or somewhere else and synchronize those in the software so that you can do some more detailed analysis.

It has relays to allow for control applications, and importantly, it supports both DNP3 and Modbus. You can use either of these protocols, and in fact, you can use them both at once if you have a need for more than one type of communications protocol.

How the Seeker Is Often Used

It’s used as a PQ investigation tool. This would be similar to using an Eagle or a Revolution for power quality troubleshooting. Here you’re more likely to use the cell option and less likely to use DNP3 or Modbus. That would typically be in a fixed situation like the observation use case, where you’re using the Seeker to observe something.

This would typically be a fixed installation, say at a substation or in a building, say on a large campus in an industrial situation, where the Seeker is permanently installed and would usually use Wi-Fi or Ethernet or perhaps cell-based communications and could be a part of a larger automation system. This is where you may have a SCADA master that would use DNP3 or Modbus to poll the Seeker for voltage and current power and harmonic information.

You could still use it as a PQ recorder in parallel. So even though it’s feeding data to a SCADA master, either through Modbus or DNP3, it’s also a full PQ recorder in parallel with that. You can still use ProVision or our cloud-based software to get a more detailed view than even what you can see in SCADA.

Modbus Overview

Jumping back to the white paper, the Seeker is a full power quality recorder that works with our standard software, but it also can be used in an automation scheme or as a slave with DNP3 or Modbus. This paper is about Modbus.

Modbus is in some ways similar to DNP3. The Seeker is the slave device, and it’s polled by the master. With Modbus, the master would open a socket to the Seeker on TCP port 502, and this would be either through a hardwired Ethernet connection or through a Wi-Fi connection or through the cell connection.

With a cell connection using Modbus, you would typically be using this inside of a private network, a Verizon private network that either the utility hosts or PMI actually also has a Verizon private network that could be used. Generally, this would be used inside private networking for security reasons.

With Wi-Fi, the Seeker can act as an access point and be a host, but more likely in a Modbus situation, it would be a client that would join an existing access point that may be present inside a facility. In that case, it gets an IP address from that access point, and the networking is similar to any other RTU that uses TCP.

Modbus Point Maps

Once the Seeker is online, it’s listening on port 502 for master connections. A Modbus master would connect to the Seeker and then poll for whatever points on the point map that it needs. These point maps are defined in these tables.

Device Configuration

The very basic ones are device configuration information, where we have the number of voltage and current channels, the firmware version, the serial number of the device, and the uptime in seconds. Those are all standard integers.

Floating Point Measurements

Then we get into the floating point values. These are actual measurements. Here we have the point numbers that correspond to the different types of data. For example, for RMS voltage, channel 1, 2, 3, and channel 4. Typically, 1, 2, 3 maps to A, B, and C, and channel 4, if it’s used, would be neutral ground voltage in most situations. Then we have current. Channel 4 for current is usually the neutral current.

Then real, reactive, and apparent power, phase angle, power factor, and displacement power factor. These are all one-second values, one-second averages. So this would be the one-second RMS voltage and current, one-second real power in kilowatts, kbar, kVA, phase angle in degrees, and this is the phase angle between voltage and current for each individual phase. These would ideally be either 0 or 30 degrees, depending on whether it’s a Y or a delta hookup. Power factor and displacement power factor.

Delta vs. Wye Configurations

If it’s a delta hookup, then only total power quantities can be measured. With a delta, it’s not possible to measure individual phase powers. For a delta configuration, the total power for real, reactive, and apparent power and power factor and displacement power factor all appear in channel 1, and the other channels, 2 and 3, are zeroed out.

Channel 4 is always an independent channel, so it’ll read real, reactive, and apparent power based on the voltage and currents for channel 4, regardless of the circuit type. So for a Y, the individual powers are available in the three phases. For a delta, the total is in channel 1.

Harmonic Magnitudes and Phase Angles

You can also read individual harmonic magnitudes and phase angles. These are harmonics starting with the first harmonic or 60 hertz all the way through to the 51st harmonic. Or 52nd harmonic, and these are valid for all four channels of voltage and for current, and these are absolute volts and currents. This is RMS current and RMS voltage harmonic magnitudes. There’s not a percentage of the fundamental. These are the raw RMS voltage and RMS current magnitudes for each frequency that we see here. These are available once per second.

We also have harmonic phase angles for voltage and for current. For voltage channel one, the reference is the 60 Hertz fundamental. So the phase angle for channel one voltage will always be zero, and then the other harmonics are referenced to channel one’s 60 Hertz value. The phase angles for the channel one harmonics are with respect to zero being the 60 Hertz fundamental. Each voltage channel is handled independently. For example, phase B, channel two’s harmonics are all referenced to that individual fundamental. The current harmonics are all referenced to the voltage channels.

It’s rare that phase angles for harmonics are needed, so we recommend if you need harmonic data to just pull the magnitudes because it’s not often that your harmonic phase angles end up being very useful. To minimize network traffic, only pull the magnitudes unless you have a specific need for the phase angles. Especially as you get up into the higher harmonic levels, those phase angle numbers are not always that useful.

We have a different point map number for each harmonic number for each channel of current also, and also the current phase angles.

Using Modbus and DNP3 Together

It’s relatively straightforward. Modbus is one of the more simple SCADA protocols. DNP3 is also supported in the Seeker, and that has a more elaborate protocol and a bit more to that. You can use Modbus and DNP3 at the same time with the Seeker. You can listen on multiple ports, and it also, while providing Modbus client functionality, is doing a full PQ recording. You can still download the Seeker in parallel with either ProVision or have it feed data up into PQ Canvass, our cloud-based power quality analysis tool.

PQ Canvass Demo

Most listeners will be familiar with their PC software already, but I’m going to show Canvass really quickly. This is PQ Canvass, and this is where PQ recordings from the Seeker go up to the cloud through the network. I can click on View Recordings, and these are recordings from the Seeker. This is similar to ProVision, but in the cloud. Here it’s in a web browser.

I can look at RMS voltage, current, and these are the strip charts with min, max, and average. Here we have RMS voltage and current. We see voltage and current. We see some voltage sags. This Seeker is actually installed in a substation, so this is on a particular feeder. We can also look at waveform captures for this recording, just like a normal PQ recording.

This is in parallel with the Modbus or DNP3 polling situation, but you can’t really get waveforms and other more advanced power quality information through a protocol like Modbus. It really wasn’t designed for that. The Seeker is perfect for applications where you have an automation scheme, you have a SCADA master that is keeping track of the basics. But if you need more information, you can also either use ProVision to download the device or have this information feed up into the cloud automatically in parallel. You can have really the best of both worlds, an RTU and also a full PQ recorder through networking.

Contact Information

If you have any questions about the white paper, give us a call anytime at 1-800-296-4120 or send an email to support@powermonitors.com. Everyone, have a great afternoon, and thanks for attending.

Have a PQ question? Ask Merlin™ — free. Send it to askmerlin@powermonitors.com or text (540) 383-3144.

Power Monitors, Inc. — Tools you Need. People you Trust.

Power Monitors, Inc. is an industry-leading product design and manufacturing firm based in Mt. Crawford, Virginia. PMI® strives to solve power quality problems by listening to our customers and working with them to design and manufacture products. Total customer satisfaction is the primary goal of all PMI® staff.

24/7 Tech Support 800.296.4120

Resources

  • White Papers
  • Videos
  • Training
  • Webinars
  • PQ Resources
  • Support

Company

  • About Us
  • Contact
  • Careers
  • Newsletter
  • Product Registration
  • Terms & Conditions
800 N Main St, Mt Crawford, VA 22841 | Toll Free 800.296.4120 | Fax 540.432.9430
© 2026 Power Monitors, Inc.