Transcript
Introduction to IEEE 1250
Today we’re gonna be talking about IEEE 1250. This is a really key standard for anyone involved in power quality. The white paper talks about how 1250 is really a gateway document, so it’s really intended to be an introduction to power quality to anyone that’s technical that needs to understand the issues around power quality.
History of IEEE 1250: The 1995 Version
IEEE 1250 was first introduced in 1995, and it started off with a much more limited scope. Its original intent was to really cover equipment that’s sensitive to voltage sags. It talks about momentary voltage disturbances, but what it really was talking about was the SEBIMA curve and the ITIC curve. So sensitive electronic equipment to voltage sags.
It introduced the SEBIMA graph, which is a way of quantifying voltage disturbances in terms of a single duration and magnitude, and then determining is that acceptable or not to electronic equipment. That curve was replaced by the ITIC curve in 1996, that you see here on the right side of the screen.
Both of these types of curves are designed to give equipment manufacturers guidelines for how rugged to design their equipment. We can have voltage sags and swells that fall in this region that are acceptable to the equipment, and then we have swells that are prohibited that could cause equipment damage, and then sags that shouldn’t damage anything but may cause the equipment to misoperate.
We have a duration on the x-axis and a magnitude on the y-axis. A single voltage sag or disturbance would fall somewhere on this graph, and depending on the region that it fell in, that’s either acceptable or not. This gave equipment manufacturers minimum standards to determine how much ride through they need in their power supplies to handle sags, and how much ruggedness and surge suppression they need to handle swells.
So 1250 was really revolved around this sort of compatibility between voltage disturbances and electronic equipment, and was fairly limited in scope, just 40 pages.
The 2011 Update
IEEE 1250 was updated in 2011, and here the scope was a bit broader. It was renamed to the Guide for Identifying and Improving Voltage Quality in Power Systems. It broadened the scope a bit, so it’s more than just sags, but it still focused more around sags than anything else.
It put in some more background information on ways to mitigate power quality issues. This is for the customer side, because voltage sags are inevitable. Well, if they’re reduced to the reasonable limits and a customer needs more help, what can they do? So it talks about surge suppressive devices, premium power solutions such as UPS or other types of sag mitigation strategies, and the economic cost of power quality.
The 2018 Version
The most recent version is the 2018 version, and here’s where it really broadened its scope to cover all aspects of power quality in an overview sense. It talks about steady state and disturbance-based power quality events and problems, and provides gateways to other documents. It’ll give you an overview of each power quality topic, and then refer you to a more specific standard for more information.
The table of contents for the 2018 version is much more beefy. It’s 63 pages, and it has more information about other types of power quality problems, including steady state like voltage regulation, voltage imbalance, waveform distortion, what generally is harmonics, interharmonics, and flicker, rapid voltage changes.
When we talk about voltage regulation, it gives an overview of voltage regulation concepts, and the same for imbalance and the other steady state and disturbance-based problems, but then gives you references to other standards to dive into more detail. For example, 519 is the standard to have limits on voltage and current waveform distortion. And for flicker, the IEEE 1453 standard is the governing document. But 1250 does more than just provide a table of other documents. It does go into some detail on the concepts behind flicker, voltage sags, distortion.
It provides a lot of good background information, and in some cases, that’s all the person needs, is what’s in 1250. But if you need to go deeper, it points you to the right direction.
The Concept of Compatibility Levels
It really introduces the concept of compatibility. We talk about this in the white paper, where we have various levels of power quality. At the smallest level, we have limits for individual devices, and we have planning levels for the utility. This is where utilities shoot for. We have levels that would generate alerts. This is the compatibility level. Any disturbance on the left side is okay with equipment. That does not interrupt function. Going beyond that, we have the immunity levels. These are the levels that equipment are actually tested to to make sure they can ride that. And then damage levels.
This is also shown on a time-based graph in the standard, where this is versus the time and disturbance magnitude. This is a very generic type of y-axis. It depends on the disturbance and how you quantify it as to what this magnitude means. The assess level is what we actually measure in the field. The planning level is what utilities shoot for, and of course, you want to be under your planning level.
Compatibility level is kind of the demarcation point. Anything below that should be perfectly fine with customer equipment. So you shoot for your planning level. You hope that you’re under that, but you definitely don’t want to exceed the compatibility level. Alarm levels are where thresholds would be exceeded. That’s where something might get shut off, a contactor threshold or a UPS or some other protective device. And then above that is where equipment is tested to. Equipment is guaranteed to at least make it to this level, and then above that is where you might start damaging equipment.
These different levels of disturbances are talked about in 1250. And power quality is about compatibility. That’s like the borderline between what the utilities try to make happen and what equipment can actually handle. Ideally we’re in this region for what’s actually happening in the field, and that gives some headroom so that if things don’t work out as intended, we still have some headroom there.
Whitepaper Overview of Power Quality Topics
Back to the whitepaper, the whitepaper first talks about that, and these different scales of disturbances correspond to those levels that I showed on the graph. Those figures are from the 1250 standard, and gives a graphical way of understanding the different types of levels that we’re talking about, from the small levels all the way up to the equipment damage level.
Then 1250 goes into more detail about individual types of power quality aspects, starting with voltage regulation—high voltage, low voltage. Then talks about voltage imbalance, both with the phase angle and magnitude imbalance on three-phase systems, and the types of problems that can cause for customer equipment.
Then it moves into voltage distortion, which is also a steady state voltage quality phenomenon, because here we’re talking about deviations from the ideal 60 hertz sine wave shape. There are various ways to quantify that. It refers readers to the 519 standard, where harmonic distortion is precisely defined, and levels are set for both utilities with voltage and customers for current.
After that, it talks about the last steady state aspect of voltage quality, which is flicker or voltage fluctuations. These generally manifest problems in terms of flickering lights. The traditional incandescent bulb that produces an irritating or visible amount of light flicker based on rapid changes in RMS voltage. It refers to the IEC and the IEEE flicker standards for more information, but the overall concept is that there’s a threshold of irritability where people will become irritated by that amount of light flicker, and there’s a threshold of visibility where they’ll see it, but not necessarily become irritated by that.
Disturbance-Based Power Quality Types
Then it moves on to the disturbance-based power quality types, and these include voltage sags and interruptions, transients such as impulsive transients and oscillatory transients. For these, it gives some guidelines, but then refers readers to the IEEE 1159 standard, which goes into more detail in defining precisely what we mean by an oscillatory transient or an impulsive transient or a sag versus a swell, and the different timescales involved, where we have temporary, momentary, and instantaneous disturbances. Those are all rigorously defined in 1159.
Frequency deviation is mentioned in 1250. That’s another steady state quality issue that’s actually pretty rarely a problem in distribution networks.
Consumer Side and Mitigation Strategies
Then it talks about the consumer side of the meter, of the susceptibility of loads to power quality issues, the typical failure mechanisms, and also talks about ways to mitigate power quality problems, both on the utility side and on the customer side.
Some of the PQ mitigation strategies involve changes on the customer side, so-called premium power solutions, as they term it, where if a customer has equipment that’s more sensitive than the normal compatibility level that a utility can provide, then the burden is on the customer to provide some sort of premium power situation with power conditioning perhaps, UPS, or other types of dynamic voltage restore or energy storage to ride through voltage sags. This could be filtering to filter emissions. Other types of solutions on the customer side when their equipment is more sensitive than is practically achievable by the utility. And the economic cost of power quality, what types of systems are economically justifiable or not.
Why Start with IEEE 1250
So the 519 standard is really a foundational document that everyone involved in power quality should start with. If you only read one IEEE standard for power quality, 1250 is the one to start with. It was written by utility engineers for utility engineers. So it’s not a dry academic paper. It’s really a good paper for folks that are directly hands-on involved in understanding power quality or dealing with power quality problems or trying to come up with solutions.
Again, if you need more information, it will refer you to the applicable IEEE standard for more detail, whether that be 1159 or 519 or possibly 1453, the other standards that govern more directly these types of power quality issues. But it’s very helpful to get an overview of power quality by starting with 1250. For some people, that’s all they may need. That gives them enough detail. But if you’re diving into the details, then 1250 is really the gateway to learn where do I go next for more information.
Join the IEEE 1250 Working Group
I encourage anyone that is involved in power quality or interested in kind of shaping these standards to join IEEE 1250 working group. It’s still an active working group. These standards are revised every few years, and there’s always room for more. What’s actively being discussed in 1250 now are issues surrounding distributed generation, high frequency noise, other types of distributed generation issues, and other types of more modern power quality issues.
Closing
That concludes the short whitepaper about 1250. Hopefully everyone is able to get a copy of this. Most utilities have access to IEEE documents. If you don’t, it’s available on the IEEE website for a small fee. If you have any questions about IEEE 1250 or the power quality standards, feel free to give us a call anytime at 1-800-296-4120, or send an email to support@powermonitors.com. Thanks for attending, and have a great day.