Specs
Inputs
AC Voltage: 0 to 300 VAC
AC Current: 0 to 1,000 Amps with CT probes
Sample Rate: 15,360 samples per second/channel; 256 samples per cycle
Channels
Voltage: 2 channels
Current: 2 channels
Measured Quantities Per Cycle
RMS Voltage: Volts
RMS Current: Amps
Real Power: Watts
Apparent Power: VAs
Reactive Power: VARs
Phase Angle: Degrees
Power Factor: Watts/VA
Displacement PF: cos (phase angle)
Power Usage: kWh, kVARh, kVAh
Accuracy
Voltage: ±0.33% of full scale
Current: ±1.0% of full scale w/o probe
Power: ±1.0% of full scale w/o probe
Phase Angle: ±1.0° w/o probe
Power Factor: ±0.02 w/o probe
Displacement PF: ±0.02 w/o probe
Safety
Pollution Degree 2: 600V CAT III
UL Listed: UL/IEC 61010
Harmonics
Voltage: to the 51st
Current: to the 51st
Measures: magnitude, phase, THD
Communications
Bluetooth® Wireless, USB
Information Storage
Interval Graph: 6.9 MB
Significant Change: 1000 records
Flicker: 1000 records
Waveform Capture: 3.75 MB
Record Settings
Interval Graphs: 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes
Significant Change: 1V to 8V in 1V steps
Flicker: User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141
Waveform Capture: Voltage and current threshold, periodic capture
Power Supply Requirements: Environmental
Voltage: 60-600VAC Channel 1 to Common (47-63Hz)
Power Consumption: 1.5 Watts max, 9VA max at 600VAC
Operating Temp: -22°F to +131°F
Humidity: Less than or equal to 85%
Shock: 60 Hz to 2 kHz, acceleration 25G
Vibration: 10 Hz to 60 Hz, amplitude 1.8mm
Max Altitude: 2.0 km (6560 ft), derated above 2.0 km
Physical Dimensions
Size: 4.375”L x 3.375”W x 1.812”H
Weight: less than 1 lb
Case: NEMA 4X
Power Fail Operation
Specifications: These recorders can operate without any input voltage for up to 2 hours. This allows it to record down to 0 volts on all channels during power outages.